Introduction

The Cordant Edge Gateway is powered by 20-57V and has a hard wire connection because it operates in a hazardous environment.

The customer is expected to supply the power supply infrastructure as part of the customer action list.

The Cordant Edge gateway (Node) must be connected to a dedicated power supply by a certified electrician on behalf of the site before Augury’s installation visit.

If the customer requests it, a power rectifier, which converts from AC to DC, can be provided by Augury at no additional cost. It must be installed and connected to the communication node by a customer-certified electrician before Augury’s installation visit.

Connect the power supply

Make sure that there’s a 20-57 VDC available to power the gateway. The power supply must be connected by a certified electrician.

1: Connect the free end of the M12 4-pin A-coded connector power cable, supplied by Augury as part of the Cordant Gateway Kit, to the power supply using the following schematics and image.

image.png

2: Separate the blue and brown reset wires and tape them using insulation tape, otherwise, the system resets itself.

AD_4nXeqsKNesP-aBDNrp9eOb_S8Mb-pfcoQwxWcIHxfHldcUwbgInSYgfQM-PwXpJ8tFlJF98ANa2UiiGuY8Y24IR1yPNRwiyebK1Roq-ZdkNEjGPz5meBOOi88JxS7Xb_KPvDVYdFxUA?key=eCnRGJGfPng-TNh_ioXOUAq1

3: Connect the cable to the M12 power connector on the bottom of the gateway.

AD_4nXc0Mp-xVfGW0dc6qA9NJwgvu3zI3dQloao_f2HQC6Q38jzHIupP7e_irp7SZ79zp5U7CuFglObwVHsYjjgr9NUgywoFBZ7vnKDcnQWpSnqWSdvAQGwdxQVtxiK9bPty9HcoJJdXxw?key=eCnRGJGfPng-TNh_ioXOUAq1

4: Check that the green LED light turns on.